“The condenser won’t pull vacuum” is a useful description of the complaint, but a poor replacement specification. The bundle might be too small. It might also be receiving warmer water than expected, holding condensate, or carrying more air than the vacuum equipment can remove. A new bundle won’t necessarily correct any of those conditions.
Record the absolute pressure and process load, then the water flow and temperatures. Add condensate level and the operating conditions at the air-removal equipment. A water temperature from the morning and a pressure complaint from the afternoon may describe two quite different duties.
Read absolute pressure and cooling-water temperature together
A pressure figure needs a reference. An absolute-pressure instrument and a vacuum gauge referenced to atmosphere won’t report the same number. Copy the instrument’s reference and units along with the reading, and mark its location on the drawing. That small amount of housekeeping avoids an unnecessary argument over apparently conflicting pressure values.
For steam, the connection between cooling-water temperature and condenser pressure is explained in the Heat Exchange Institute’s Condenser Basics. Steam condenses outside the tubes and transfers heat to water flowing inside. The document concerns power-plant surface condensers. It is useful background, but a process mixture still needs a calculation based on its own composition.
Suppose the design sheet specified cooler inlet water than the plant now supplies. That difference needs resolving before anyone declares the bundle undersized. Then there is the flow question. Water has to get past the strainer and through the valves before it reaches the bundle. A pump that is switched on can still be delivering too little through a restriction, so use a flow reading rather than its running indication.
A note of “normal pressure” in an old maintenance log is less useful than the full commissioning sheet. Pressure drop changes with flow, even when the tubes haven’t acquired a new deposit. The older sheet should show enough of the operating condition to decide whether today’s reading is a fair comparison.
Follow the noncondensable gas to its outlet
Consider what leaves the condenser as liquid and what doesn’t. The noncondensable gas stays gaseous under the stated conditions. Giving it more cooling surface won’t provide an exit. That job belongs to the gas outlet, its connecting path and the air-removal equipment at the far end.
HEI identifies air leaking into equipment under vacuum as one source of that load. A process plant may have others. Nitrogen introduced upstream, for instance, doesn’t cease to matter because the main stream is called vapour on the process diagram. Give it its own entry in the composition and flow information sent to the designer.
Check air ingress and removal capacity
The timing can narrow the investigation. If performance changed straight after a shutdown, list the joints that were opened and reassembled. If it changed with a new operating recipe, compare the incoming gas load with the previous one. Neither proves a fault, but each is a more useful starting point than an undated complaint about poor vacuum.
The installed vacuum equipment sets the next questions. An ejector review includes the steam supplied to it. A liquid-ring pump review includes the service-liquid conditions. Work from the specification for that particular equipment, with its supplier involved where needed. A general note that “the vacuum system is running” leaves out the conditions needed to assess its capacity.
This investigation follows the plant’s leak-testing and isolation procedures. Opening a connection on a running vacuum system is not an acceptable shortcut to finding a suspected restriction.
Keep pressure losses visible
A satisfactory reading at the vacuum equipment can be misleading if the complaint comes from the process vessel. Compare both locations during the same run, using the installed instruments. Then look at what lies between them. The connecting pipe, outlet and valves all carry gas; a restriction along that route can separate the two operating conditions.
In an enquiry, “allowable pressure drop” needs a side and a flow basis attached to it. Give the vapour-path allowance separately from the water-side allowance. For gas volumes, state whether the figure is at actual or reference conditions. Under vacuum, that distinction matters to the flow the equipment has to handle.
Check the condensate drain before changing the bundle
A drain nozzle is only the start of the condensate route. The receiving pressure and available elevation determine what drives the liquid along it. Check the whole route against the approved drawing. A pipe alteration made to gain floor space may be relevant even though nobody changed the condenser itself.
HEI’s vacuum condenser drainage guide discusses steam-ejector condenser drainage, including how changing condensate loads and inadequate drainage arrangements can cause backup. It also distinguishes loop seals from mechanical drainers. Those arrangements depend on the system; the guide’s example dimensions should not be copied into an unrelated installation.
A rising level during higher load is worth reporting. So is a change in the receiving vessel’s pressure. Give the designer those observations before replacing a drainer or altering pipework. The original arrangement may have been adequate for a set of conditions that the plant no longer has.
It is tempting to choose the first plausible explanation and stop looking. Yet a drainage fault doesn’t rule out warmer cooling water on the same day. After a correction, repeat the relevant readings at a comparable load. Did the pressure return to the expected condition, or was only part of the complaint resolved? Keep that result with the original fault sheet.
Specify a serviceable shell-and-tube replacement
After that work, the replacement enquiry has something solid behind it. Grano’s シェルアンドチューブ式熱交換器 consists of a shell and a tube bundle. Large flows and low pressure-drop duties are among the uses of this range. The heat-transfer area can be made to customer requirements. These are starting points for selection; the measured process conditions determine the duty to quote.
Tube-side access and materials
The shell-and-tube range includes stainless steel, carbon steel and copper material options. Alongside the shell and bundle are the end components, gaskets and supports. Units can be configured for different production requirements and heat-exchange areas, with access for cleaning and maintenance. Applications include petrochemical, pharmaceutical, steel and HVAC service.
Read the proposed drawing as a maintenance job. Can the technician reach the surface that needs cleaning once the pipes are in place? Then read it as a design review. Copper being available doesn’t mean it suits the process fluid. Nor does an internal-pressure figure establish suitability under vacuum. Those decisions need the selected unit’s design basis, with its applicable external-pressure condition stated.
A separate plate exchanger in the cooling circuit
An intermediate water circuit, where fitted, adds another place to investigate. In a detachable plate unit, bolts clamp the corrugated heat-transfer plates between the frame’s clamping plates. Guide rods keep the plates located. Openings at their corners connect the passages through the pack; the gaskets seal it and define the channels. The corrugations disturb the liquid flowing through them.
Opening the pack exposes the plates for cleaning and examination. Scale makes heat transfer poorer, while dirty or obstructed channels can increase pressure drop. A plate perforated by corrosion can let the two fluids mix. Such a fault is in the intermediate exchanger, but its effect can reach the condenser through the cooling-water circuit.
On the herringbone plate, four flow openings accompany the pressed corrugation, with a sealing groove around the edge. The specified A and B plates alternate; an A/A or B/B pair is outside that sequence. Check the order if performance changed just after rebuilding. Also examine the gasket faces: the upper and lower sealing surfaces should be smooth and flat, without bubbles, pits or flash that interferes with the seal.
There is no reason to add an intermediate circuit merely to follow this check. Where one exists, its temperature differences and pressure losses are part of the plant’s cooling path and need to be accounted for.
Take a complete fault record to the supplier
送信 粒 the marked drawing with duty sheets for normal and worst-case operation. Include gas composition, absolute pressure, cooling-water conditions and the condensate route. There is a reason to attach both the original design sheet and today’s measurements: they show whether the requested replacement faces the old duty or a changed one.
Read the quotation back against that information. The duty and pressure losses on both sides need to be stated, as do materials, design pressures and the space needed for service. Keep the gas outlet and drain arrangement on the review drawing. A completed heat-transfer calculation is no reason to stop checking where the gas and liquid will go.

